Scott’s Custom Renovation & Construction Phone: (813)-433-8556

9621 N. Ojus Dr Fax (813)-983-8349

Tampa, Fl

33617

BUYER’S HOME INSPECTION REPORT

Buyer(s): Date: 7/19/2005 Time: 6:30 PM

Property Address: City: Zip:

Listing Company: Agent(s):

Phone: FAX:

Buyer’s Company: Agent(s):

Phone: FAX:

Vacant Occupied Furnished Unfurnished

Single Story Two Story

Attendees: Buyer Seller Selling Agent Listing Agent Inspector Only

Inspector: Dennis Beerman

IMPORTANT AGREEMENTS AND LIMITATIONS

This is a visual inspection only. We inspect only what we see. We do not disassemble anything. We do not inspect for any environmental issues such as lead paint, asbestos, etc. We do not inspect for compliance to building codes, soil analysis, adequacy of design, capacity, efficiency size, value, flood plain location, pollution or habitability. Please remember that older houses do not meet the same standards as newer houses, even though items in both might be performing the function for which they are intended. We do not hold ourselves to be specialists for any particular item; nor are we engineers. This inspection report covers only the items listed in the report which are reasonably observable, and are based only on the present condition of those items at the time of inspection.

This is a visual inspection limited in scope by (but not restricted to) the following conditions:

Furniture, storage, appliances and/or wall hangings are not moved to permit inspection and may block defects.

There is no responsibility expressed or implied for latent defects, or for defects not reasonably observable at the time of the inspection, or for defects that would require the removal of major or permanent coverings for observation. No representation is made concerning any condition other than the operability of any item. No representation is made as to the future performance of any item. There are no warranties, either expressed or implied. When an item is noted as non-operational or in need of repair, replacement or further evaluation by a specialist, the purchaser agrees to contact a qualified specialist to make further evaluations of the item before you purchase the home.

Dispute resolution: In the event a dispute arises regarding this inspection, the purchaser agrees to notify inspector so as to give a reasonable opportunity to re-inspect the property. If we are unable to satisfy this dispute within 30 days of the grievance, then any claims resulting are limited to the price of the inspection.

Defense Costs: In the event the purchaser files suit against the Scott’s Custom Renovation & Construction, or its inspector, the purchaser agrees to pay all the company’s legal fees, costs of expert witness, court costs, costs of depositions and all other such expenses incurred by Scott’s Custom Renovation & Construction if the purchaser fails to prevail in the lawsuit.

Exclusivity: The report is prepared exclusively for the Client(s) named and is not transferable to anyone in any form. Client(s) gives permission for Scott’s Custom Renovation & Construction to discuss report findings with real estate agents, specialists or repair persons for the sake of clarification.

Inspected 7/19/2005

Year Built: 1997 Square Feet: 2008 4 Bedroom

2 Bath Family Room Living Room

Dining Room Laundry Room 2-Car Garage

Stucco exterior Patio / Screen Enclosure

Exterior

_____________________________________________________________________________________

Sidewalk: N/A Concrete Asphalt Stone

Condition: Cracked Uneven Settled

Comments:

_____________________________________________________________________________________

Path: N/A Concrete Asphalt Stone

Condition: Cracked Uneven Settled

Comments:

_____________________________________________________________________________________

Front Patio: N/A Concrete Brick Stone Tile

Condition: Cracked Uneven Settled

Comments:

_____________________________________________________________________________________

Rear Patio: N/A Concrete Brick Stone Tile

Condition: Cracked Uneven Settled

Comments:

Tile inside screen enclosure, concrete outside enclosure.

Screen door and screen panel East of door torn or not secured.

Some normal settlement cracks in concrete outside of screened area. _____________________________________________________________________________________

Deck/Porch: N/A Wood Other :

Condition: Cracked Rotting Broken Needs Bracing Loose Rails Loose Steps

Comments:

_____________________________________________________________________________________

Steps: N/A Concrete Brick Stone Wood Other :

Handrail

Condition: Cracked Rotting Broken Needs Bracing Loose Rails Uneven

Comments:

____________________________________________________________________________________

Trim: Wood Stucco Vinyl Other :

Condition: Cracked Rotting Open Joints Needs Paint

Comments:

_____________________________________________________________________________________

Soffit: Wood Vinyl Metal

Condition: Cracked Rotting Sagging Open Joints Dents Needs Paint

Comments:

Ventilated metal soffit throughout.

_____________________________________________________________________________________

Fascia: Wood Vinyl Metal Other : Engineered Material

Condition: Cracked Rotting Sagging Open Joints Dents Needs Paint

Comments:

_____________________________________________________________________________________

Gutters: N/A Partial Full

Built-in Aluminum Copper Galvanized Wood Continuous

Condition: Loose/Sagging Open Joints Needs Cleaning

Comments:

Gutters on screen enclosure section of rear porch.

_____________________________________________________________________________________

Windows: Wood Aluminum Vinyl Clad Thermal

Single Hung Double Hung Casement Fixed Jalousie Horizontal Sliding

Condition: Cracked Rotting Missing Trim Screen Repair Needs Caulk Needs Paint

Comments:

Guest bathroom screen torn.

Note: Hurricane shutters are not included in this inspection.

_____________________________________________________________________________________

Driveway: Concrete Asphalt Brick Mulch Other :

Condition: Cracked Uneven Heaving

Comments:

_____________________________________________________________________________________

Garage: N/A Attached Detached

1 Car 2 Car 3 Car 4 Car

Comments:

_____________________________________________________________________________________

Garage Door: Operational Automatic opener Needs Adjustment Needs Repair Needs Paint

Unable to access or operate

Comments:

Opener safety sensors checked and operational.

_____________________________________________________________________________________

Carport: N/A Attached Detached

1 Car 2 Car 3 Car 4 Car

Comments:

_____________________________________________________________________________________

Fencing: Wood Metal Vinyl Other :

Condition: Rotting Rusting Needs Repair Needs Paint

Comments:

Unable to check operation of gates.

_____________________________________________________________________________________

Exterior Doors: Wood Fiberglass Insulated Steel Other

Condition: Rotting Rusting Needs Repair Needs Paint

Comments:

Exterior door to Garage solid core wood door.

_____________________________________________________________________________________Grading & Drainage:

Comment:

Front yard slopes to street. Rear slopes towards house. No problems observed.

Note: Foundation area surface or subsurface drains are not tested.

_____________________________________________________________________________________

Structure

_____________________________________________________________________________________

Foundation: Slab on Grade Concrete Block Piers

Condition:

Comments:

_____________________________________________________________________________________

Exterior Walls: Block Brick Stone Stucco Wood Siding Wood Shingle

Asbestos Shingle Aluminum Siding Vinyl Siding Other :

Condition: Cracked Rotting Needs Paint

Comments:

Some settlement cracking in block wall observed (see photo 1). Some stucco cracking observed.

These are expected conditions for a house this age. Stucco requires periodic maintenance to repair cracking. Suggest a good exterior polyurethane caulk along with an elastomeric paint when next painted.

Suggest cutting stucco finish to 8 inches above grade to allow for observation of any future potential subterranean termite tunnels. _____________________________________________________________________________________

Roof Structure: Engineered Truss Rafters

OSB/Wafer board Plywood

Comments:

Only partial roof over attic was able to be inspected from the underside.

Note: Structural components concealed behind finished surfaces could not be inspected. Engineering or architectural services such as calculation of structural capacities, adequacy, or integrity are not part this inspection.

_____________________________________________________________________________________

Roofing

_____________________________________________________________________________________

Roof: Architectural 3-tab Wood Slate Tile Built-up Tar & Gravel Other :

Condition: Loose Missing Curled Cracked

Comments:

Roof in good condition.

Recommendations:

Removal of satellite dish mount and seal holes along with other holes in roof with liquid tar material (see photo 2) to avoid potential leak spots.

_____________________________________________________________________________________

Chimney: N/A Brick Masonry Stucco Other :

Cricket: Yes No

Chimney Cap: Yes No

Comments:

_____________________________________________________________________________________

Skylights: N/A

Comments:

_____________________________________________________________________________________

Method of Inspection: Walked Roof Inspected from ladder at eave

Note: Not all of the underside of the roof sheathing is inspected for evidence of leaks. Evidence of prior leaks may be disguised by interior finishes. Estimates of remaining roof life are approximations only and do not preclude the possibility of leaking. Leakage can develop at any time and may depend on rain intensity, wind direction, and other factors.

Antennae, chimney/flue interiors which are not readily accessible are not inspected and could require repair. Roof inspection may be limited by access, condition, weather, or other safety concerns.

_____________________________________________________________________________________

Plumbing

_____________________________________________________________________________________

Interior Plumbing:

Supply Lines: Copper Galvanized CPVC PVC Polybutylene

Other :

Waste Lines: Cast Iron PVC Other :

Water Heater: Electric Gas

Size: 40 gallons

Comments:

Waste clean-out located under kitchen sink.

Note: Pipes and plumbing in walls, in or under concrete slabs or concealed by personal effects and their quality, condition or purification of water is not included in this inspection.

_____________________________________________________________________________________

Exterior Plumbing:

Water Supply Source Well Public Supply

Main Water Valve Location Meter Well Tank Other :

Waste Disposal Public Sewer Septic

Fuel Shut-off Valve N/A Meter

Other Components Sprinkler System

Comments:

Secondary water shut-off valve located at South West corner at water conditioner.

Damaged sprinkler riser observed in yard at North West corner (see photo 3).

Note: Water conditioning systems, solar water heaters, fire and lawn sprinkler systems, and private waste disposal systems are not included in this inspection.

_____________________________________________________________________________________

Insulation/Ventilation

_____________________________________________________________________________________

Attic Access Hatch Pull Down Door Location: Garage ceiling

Attic Insulation Loose Fill Batts Other :

Approximate Thickness: 8 inches R -rating R- 30

Roof Ventilation Ridge Vents Gable Vents Soffit Vents Power Ventilator

Exhaust Fan/Vent Locations Kitchen Bath(s) Dryer

Comments:

Attic access trim insecure (see photo 4).

Hatch (1/2” drywall) deteriorated at edges.

Two (2) lead/acid batteries observed in attic.

Insulation thickness based on the observable portions of the attic area only, and may not be a true reflection of the entire home.

Recommendations:

Repair access hatch trim. Hatch rests on trim and is a potential safety hazard.

Replace hatch (1/2” drywall).

Removal of two (2) lead/acid batteries in attic.

Note: Insulation/ventilation type and levels in concealed areas are not inspected. Insulation and vapor barriers are not disturbed and no destructive test (such as cutting openings in walls to look for insulation) are performed.

Potentially hazardous materials such as Asbestos and Urea Formaldehyde Foam Insulation (UFFI) cannot be positively identified without a detailed inspection and laboratory analysis, and are beyond the scope of this inspection.

No analysis of indoor air quality is performed.

Any estimates of R values or depths are rough average values.

_____________________________________________________________________________________

Mechanical

_____________________________________________________________________________________

Air Conditioner:

Compressor: Trane XE1000 4 ton Air Handler: Trane XE1000 4 ton

Type: Central Split System Package System Heat Pump Number of Zones: 1

Location: Compressor: Outside / East wall

Air Handler: Inside Garage

Temperature Return: 75 0 F

Temperature at Register: 57 0 F

Duct System: Flex Ductboard Metal

Return Grill Location: Hallway ceiling at guest bath

Return Grill Filter: ____ X ____

Comments:

No return filter present at time of inspection. This could lead to dirt collection on coils, and result in in-efficient performance.

Air handler platform appears damaged (soft) due to condensation dripping from supply lines and drain pipe.

Recommendations:

Inspection and cleaning of system by licensed professional.

Further inspection of platform to determine extent of damage, if any.

Installation of return air filter.

Note: Temperature differential is the difference between the input and output temperature. 14 to 22 degrees F is ideal.

Note: Determination of balancing or system sizing is not a part of this report.

_____________________________________________________________________________________

Electrical

_____________________________________________________________________________________

Main Panel Location: East wall in Garage

Main Cut-off Switch: Yes No

Location: Meter Panel

Grounded: Rod Water Pipe Pipe Not Visible

Amps Capacity: 150

Voltage 110 220

Wiring: Copper Aluminum

Panel Box: Circuit Breaker Fuse

Smoke Detectors: N/A Operational Non-operational Wired in series

Ceiling Fans: N/A Operational Non-operational

Doorbell: N/A Operational Non-operational

GFCI No Outlet Breaker Operational Non-operational

Location: Baths and Kitchen

Comments:

All smoke alarms are missing batteries used as back-up in the event of power failure.

Residence is equipped with a Security System.

Recommendations:

Installation of back-up batteries in all smoke alarms for proper functioning during periods of power outage.

Note: Inspection and operation of security systems are not included in this report.

_____________________________________________________________________________________

Interior

_____________________________________________________________________________________

Stairs: N/A Handrail Secure Handrail Insecure

Countertops: Laminate Granite Tile Other

Cabinets: Laminate Surface Wood _____________________________________________________________________________________

Foyer

Ceilings: Drywall Plaster Paneling Wallpaper Tile

Walls: Drywall Plaster Paneling Wallpaper Tile

Flooring Carpet Tile Wood Sheet Goods

Comments:

_____________________________________________________________________________________

Dining Room

Ceilings: Drywall Plaster Paneling Wallpaper Tile

Walls: Drywall Plaster Paneling Wallpaper Tile

Flooring Carpet Tile Wood Sheet Goods

Comments:

Stain observed on ceiling (see photo 5).

_____________________________________________________________________________________

Living Room

Ceilings: Drywall Plaster Paneling Wallpaper Tile

Walls: Drywall Plaster Paneling Wallpaper Tile

Flooring Carpet Tile Wood Sheet Goods

Comments:

_____________________________________________________________________________________

Master Bedroom

Ceilings: Drywall Plaster Paneling Wallpaper Tile

Walls: Drywall Plaster Paneling Wallpaper Tile

Flooring Carpet Tile Wood Sheet Goods

Comments:

Plug wire protruding through West wall (see photo 6). If this is for the operation of the water conditioning system, a separate GFCI protected exterior box should be installed.

Damaged window trim (see photo7).

Recommendations:

Removal of wire through wall and installation of GFCI exterior rated outlet box if required for water conditioning system.

_____________________________________________________________________________________

Master Bathroom

Ceilings: Drywall Plaster Paneling Wallpaper Tile

Walls: Drywall Plaster Paneling Wallpaper Tile

Flooring Carpet Tile Wood Sheet Goods

Comments:

Drain stopper missing on left side sink (see photo 8).

Minor damage to vinyl at entry door (see photo 9).

_____________________________________________________________________________________

Bedroom 1 (North West corner)

Ceilings: Drywall Plaster Paneling Wallpaper Tile

Walls: Drywall Plaster Paneling Wallpaper Tile

Flooring Carpet Tile Wood Sheet Goods

Comments:

Closet door is not engaged in track and has the potential for falling out of opening (see photo10).

Trim at closet door damaged (see photo 11).

Recommendations:

Adjustment/re-installation of closet door.

_____________________________________________________________________________________

Bedroom 2 (North East corner)

Ceilings: Drywall Plaster Paneling Wallpaper Tile

Walls: Drywall Plaster Paneling Wallpaper Tile

Flooring Carpet Tile Wood Sheet Goods

Comments:

Ceiling fan ceiling trim missing, leaving wiring exposed (see photo12).

Closet door off track, and has the potential for falling out of opening (see photo 13).

South wall outlet cover plate secured with improper screw (see photo 14). If tightened further, could crack and damage outlet.

Recommendations:

Installation of fan trim or replace if parts are not available.

Adjustment/re-installation of closet door.

Replacement of receptacle cover plate screw with proper size.

_____________________________________________________________________________________

Bedroom 3 (South East corner)

Ceilings: Drywall Plaster Paneling Wallpaper Tile

Walls: Drywall Plaster Paneling Wallpaper Tile

Flooring Carpet Tile Wood Sheet Goods

Comments:

_____________________________________________________________________________________

Hall Bath

Ceilings: Drywall Plaster Paneling Wallpaper Tile

Walls: Drywall Plaster Paneling Wallpaper Tile

Flooring Carpet Tile Wood Sheet Goods

Comments:

Slight burn mark on laminate vanity top (see photo 15).

Tub stopper broken (see photo 16).

Tub diverter pulled away from wall (see photo 17). Potential for water intrusion behind tile.

Valve handle cracked. Potential for injury during operation of valve..

Recommendations:

Adjustment to tub diverter to bring it flush with tile and caulk.

_____________________________________________________________________________________

Laundry

Ceilings: Drywall Plaster Paneling Wallpaper Tile

Walls: Drywall Plaster Paneling Wallpaper Tile

Flooring Carpet Tile Wood Sheet Goods

Washer : N/A Operational Non-operational Admiral

Dryer: N/A Operational Non-operational Kenmore

Comments:

Door stop missing rubber tip.

Large hole in drywall behind dryer at dryer vent location (see photo 18). May result in heat infiltrating through attic into residence.

No load available to cycle washer.

Recommendations:

Replacement of drywall and installation of proper vent connection.

Family Room

Ceilings: Drywall Plaster Paneling Wallpaper Tile

Walls: Drywall Plaster Paneling Wallpaper Tile

Flooring Carpet Tile Wood Sheet Goods

Comments:

Hollow sound noted under one (1) tile. Some grout missing. Homeowner aware of and has replacement tiles.

A hollow sound is an indicator that there is a void of thinset under the tile, and has the potential to crack.

Recommendations:

Replacement of tile and surrounding grout.

_____________________________________________________________________________________

Kitchen

Ceilings: Drywall Plaster Paneling Wallpaper Tile

Walls: Drywall Plaster Paneling Wallpaper Tile

Flooring Carpet Tile Wood Sheet Goods

Cooktop: N/A Electric Gas Coil Burners Smooth Top

Oven: N/A Electric Gas Self Clean Convection

Setting: 350 0 F Temp: 345 0 F

Setting: 400 0 F Temp: 375 0 F

Range Hood: N/A Vented Non-vented Microwave

Microwave: N/A Countertop Over Range HotPoint

Disposal: N/A Operational Non-operational Badger ½ HP

Dishwasher: N/A Operational Non-operational Maytag

Refrigerator: N/A

Freezer: N/A

Ice Maker: N/A

Comments:

Differences between oven setting and actual temperature are common. These temperatures are given as a reference for accuracy of oven settings.

Disposal inoperable.

Small chips in countertop laminate at right of range, and above dishwasher.

Small crack in corner of tile at entry from Family Room. Tile is secure, and no repair recommended.

Improper repair on T-connection under sink (plugged with a screw). Potential exists for future leaks. (see photo 19).

The saddle type connection on the sink drain is non-functional and has the potential to leak (see photo 20).

Sink base cabinet shows evidence of prior water damage and is sagging.

Recommendations:

Repair or replacement of disposal.

Replacement of piping to eliminate T-junction.

Replacement of drain pipe section to eliminate saddle connection.

Note: The following is not included in this inspection: clocks, timers and automatic cooking or cleaning modes. Microwaves are not checked for radiation leakage.

_____________________________________________________________________________________

Garage

Ceilings: Drywall Plaster Paneling Wallpaper Tile

Walls: Drywall Concrete Block Paneling Tile

Flooring Concrete

Comments:

Drywall damage on South wall (see photo 21).

Attic hatch and trim repair as noted under Insulation/Ventilation section of this report.

_____________________________________________________________________________________

PHOTOS

Photo 1

Photo 2

Structure / Exterior walls

Roofing / Roof

Photo 3

Photo 4

Plumbing / Exterior Plumbing

Insulation/Ventilation / Attic Access

Photo 5

Photo 6

Interior / Dining Room

Interior / Master Bedroom

Photo 7

Photo 8

Interior / Master Bedroom

Interior / Master Bathroom

Photo 9

Photo 10

Interior / Master Bathroom

Interior / Bedroom 1

Photo 11

Photo 12

Interior / Bedroom 1

Interior / Bedroom 2

Photo 13

Photo 14

Interior / Bedroom 2

Interior / Bedroom 2

Photo 15

Photo 16

Interior / Hall Bath

Interior / Hall Bath

Interior / Hall Bath

Interior / Hall Bath

Photo 17

Photo 18

Interior / Hall Bath

Interior / Laundry

Photo 19

Photo 20

Interior / Kitchen

Interior / Kitchen

Photo 21

Interior / Garage